Commercial Kitchen Exhaust & Ducting: Types, Cost & Rules

Commercial kitchen exhaust guide for Indian restaurants: hood types, ducting, fresh air, ESP and scrubbers, cleaning frequency, fire safety and 2026 costs.

15 min read · Updated 2026-11-23 · 22 FAQs answered

A commercial kitchen exhaust system has four parts that must be designed together: the hood over the cooking line, the duct that carries grease-laden air out, the fan that pulls it, and a fresh-air supply that replaces what you remove. In Delhi NCR, a stainless steel hood is commonly listed at roughly ₹2,300–₹5,500 per running foot before ducting, fans and fire suppression, and the duct needs regular grease cleaning to avoid fire risk. This guide covers types, sizing basics, materials, pollution control, cleaning schedules and logs, installation, maintenance and realistic costs.

Why the exhaust system matters more than you think

A poorly designed exhaust shows up fast:

  • Heat: staff productivity drops and attrition rises in a kitchen that sits at very high temperatures in May and June.
  • Smoke in the dining room: guests notice before you do.
  • Fire risk: grease builds up in hoods and ducts, and a duct fire can spread beyond the kitchen.
  • Neighbour and landlord complaints: smoke, odour and fan noise are among the most common reasons for disputes with malls, RWAs and adjoining shops.
  • Approvals: fire consultants, mall fit-out teams and insurers will look at the hood, ducting route and suppression system.

Get this designed before interiors are finalised. Changing a duct route after the false ceiling is done is expensive. If you are still at the planning stage, our restaurant opening checklist shows where exhaust design fits in the sequence.

Start with the cooking line

The exhaust is sized to the equipment under it, so fix the cooking line first using our commercial kitchen equipment checklist. For each appliance, note:

  • Type and fuel (gas range, tandoor, fryer, wok, griddle, oven, steamer)
  • Width and depth
  • Whether it produces grease, smoke, heat only or steam only
  • Hours of use per day

Group grease- and smoke-producing equipment on one wall under one hood where possible. Keep steam-only equipment such as dishwashers under a separate condensate hood. Our LPG vs PNG guide covers the fuel side, which also affects gas leak detection near the hood.

Types of kitchen hoods

Hood type Where it is used Notes
Wall-mounted canopy Cooking line against a wall (most common) Simple and efficient; overhang beyond the cooking equipment on all open sides improves capture
Island canopy Cooking line in the middle of the kitchen Needs more exhaust air because it is open on all sides
Low-profile or back-shelf hood Low ceilings, small counters Sits close to the equipment; limited to lighter cooking
Water-wash hood High-grease, high-volume kitchens Built-in washing of the grease plenum; costlier
Condensate or steam hood Over dishwashers, steamers Handles steam and moisture, not grease

As a reference, the US International Mechanical Code requires canopy-type grease hoods to overhang the cooking surface by at least 6 inches on all open sides. Indian vendors do not follow one fixed standard, so write the overhang into your drawing.

Filters: baffle vs mesh

  • Baffle filters (SS or aluminium) force air to change direction so grease drops out. They are the standard for commercial kitchens, easier to clean and act as a flame barrier.
  • Mesh filters clog quickly with heavy grease and are harder to clean. They are better suited to light-duty use.

Ask your vendor for removable baffle filters sized so a staff member can lift them out and soak them.

Exhaust sizing and CFM basics

Exhaust airflow is measured in CFM (cubic feet per minute) or CMH (cubic metres per hour). One CFM is about 1.7 CMH. Indian fan quotes often use CMH, while hood design guides usually use CFM.

Duty levels

Hood airflow depends on how hot and greasy the appliances are. The US model codes group them roughly like this:

Duty level Typical appliances
Light Ovens, steamers, kettles
Medium Ranges, griddles, fryers
Heavy Charbroilers and woks
Extra-heavy Solid-fuel cooking (wood, charcoal)

Most Indian kitchens with a Chinese range, tandoor and fryers sit in the medium to heavy band. With coal tandoors banned in Delhi, extra-heavy solid-fuel cooking should be rare.

Code reference rates per running foot

The International Mechanical Code has listed minimum exhaust rates per linear foot of hood for unlisted hoods. Commonly cited values are:

Hood type Light Medium Heavy Extra-heavy
Wall-mounted canopy (CFM per ft) 200 300 400 550
Single island canopy (CFM per ft) 400 500 600 700

These figures differ between code editions and local amendments, and listed hoods tested by manufacturers can work at other rates. Use them as a sense check on vendor proposals, not as an Indian legal requirement.

Worked example

A 10-foot wall-mounted canopy over a medium-duty Indian range and fryers:

  • 10 ft × 300 CFM per ft = 3,000 CFM
  • 3,000 CFM × 1.7 ≈ 5,100 CMH

If the same 10 feet also covers two Chinese wok burners, the heavy-duty rate (400 CFM per ft) gives 4,000 CFM, or roughly 6,800 CMH. This is why Indo-Chinese kitchens need bigger fans and ducts than a dal-and-curry kitchen of the same size.

Duct velocity

Air must move fast enough in the duct to carry grease out, but not so fast that the system gets noisy and expensive to run. US model codes have used a minimum of 500 feet per minute (about 2.5 m/s) in grease ducts, and plan-check guidance commonly caps it around 2,500 fpm. Ask your vendor what design velocity they used and how they sized the duct cross-section from it.

Ducting: materials and construction

Indian vendors commonly offer GI (galvanised iron), MS (mild steel) or SS ducting. Listings show GI kitchen ducts commonly in 0.6–0.8 mm sheet and MS or SS exhaust ducts from about 1 mm to 2 mm, but there is no single Indian standard that vendors follow.

As a reference, the US standard NFPA 96 (widely used for commercial kitchen grease ducts) requires:

  • Carbon steel of at least 1.37 mm (16 MSG) or stainless steel of at least 1.09 mm (18 MSG)
  • Continuously welded, liquid-tight joints, so grease cannot leak out of seams
  • Clearance from combustible materials, often cited as 18 inches for single-wall unenclosed ducts

US codes also prohibit dampers inside grease ducts, because they trap grease and block airflow in a fire.

What to ask your vendor:

  1. Which standard are you building to, and what is the sheet thickness?
  2. Are joints welded or riveted and sealed?
  3. Where are the cleaning access doors, and can a cleaner actually reach them?
  4. Does the duct slope back towards the hood or a grease collection point?
  5. How is the duct routed through other floors or false ceilings? Does it need fire-rated enclosure?
  6. Where does the exhaust discharge, and is it away from windows, fresh-air intakes and neighbours?

Thin, riveted GI ducting is cheaper upfront but harder to clean and more likely to leak grease. For high-grease menus such as Indo-Chinese wok cooking, tandoor, grills and fryers, budget for heavier welded ducting.

Exhaust fans

  • Centrifugal (blower) fans handle the static pressure of long duct runs and filters better than simple axial fans.
  • Ideally the motor sits outside the grease airstream (belt-driven or external-motor designs), so grease does not coat it.
  • Specify airflow (CMH) and static pressure in the quote, not just motor HP.
  • Add a speed controller or VFD if you want to run lower speeds during off-peak hours and save electricity.
  • Fit anti-vibration mounts and plan for noise, especially if the fan sits on a terrace near residences.

Fresh air (make-up air)

Every cubic metre you exhaust has to be replaced. If it isn't, air gets pulled in through doors, drains and gaps, the kitchen heats up and the hood captures smoke less effectively.

  • A fresh-air unit (fan with filter, sometimes with evaporative or treated air) supplies air into the kitchen.
  • The kitchen is usually kept slightly negative compared with the dining area, so cooking smells don't drift out to guests.
  • Introduce fresh air away from the hood edge so it doesn't blow smoke out from under the canopy.

Industry commentary often suggests supplying fresh air at around 75–80% of the exhaust volume, with the balance drawn from the dining area, but that is a rule of thumb rather than a code figure. The US Uniform Mechanical Code limits negative pressure in the cooking area to 0.02 inch water column. We couldn't find an Indian rule that fixes the fresh-air percentage. Ask a mechanical engineer or HVAC consultant to size it from your exhaust volume, and check guidance from the National Building Code and ISHRAE.

Exhaust needs by cuisine and format

Format Main exhaust challenge What to plan for
North Indian Tandoor heat, gravy steam, frying Hood over tandoor with good overhang; gas or electric tandoor in Delhi
Chinese and Indo-Chinese Heavy wok smoke and grease Heavy-duty airflow, welded ducts, frequent filter cleaning
Café Light grilling, ovens, coffee steam Smaller hood over grill or oven; good general ventilation
Bakery Oven heat and steam Heat extraction over ovens; condensate handling for steam
Cloud kitchen Long hours, high volume, small space Compact but correctly sized system; strict cleaning schedule; check shared exhaust in aggregator-style facilities

Cloud kitchens often fit a hood that suits the size of the room rather than the menu. If you are budgeting a delivery kitchen, our cost to open a cloud kitchen in Delhi guide shows where exhaust sits in the total.

Pollution control: ESP, scrubbers and odour control

Delhi NCR has stricter scrutiny of air pollution than most cities. Options to reduce visible smoke and odour at the discharge:

Device What it does Approx. cost note
Electrostatic precipitator (ESP) Charged plates trap fine smoke and grease particles One Indian listing shows a dry kitchen ESP at about ₹1.2 lakh per piece; sizing varies
Wet scrubber Water spray or bath washes particles and some odour out of the air Project-based quote
Activated carbon or odour filter Adsorbs cooking odours after particle removal Consumable filters need replacement

Points to keep in mind:

  • Delhi tandoor order: in December 2025, the Delhi Pollution Control Committee (DPCC) ordered a ban on coal and firewood tandoors at hotels, restaurants and open eateries, under the Air (Prevention and Control of Pollution) Act. Establishments were told to use electric, gas or other approved clean-fuel systems. Confirm the order's current status with DPCC.
  • No verified blanket ESP mandate: we could not verify a citywide rule requiring every restaurant to install an ESP or scrubber. Requirements can come from DPCC directions or consent conditions, mall fit-out rules or complaints. Ask DPCC and your landlord before you design.
  • Maintenance is the catch: an ESP with dirty plates doesn't do much. Build plate cleaning into your schedule.
  • Outside Delhi: Noida and Ghaziabad fall under Uttar Pradesh, and Gurgaon and Faridabad under Haryana, so pollution control directions come from different state boards. Check with the relevant board and your landlord.

Working with malls, landlords and RWAs

In Delhi NCR, many exhaust problems are not technical but about permission. Before you pay an advance, settle these points with whoever controls the building:

  • Malls and food courts often have a fit-out manual that specifies hood material, duct route, shaft location, suppression system and cleaning frequency. Ask for it before you take vendor quotes, so every vendor prices the same specification.
  • High-street shops and markets may have no shaft at all, which forces a duct up the rear wall to the terrace. Get the landlord's written consent for the route and the fan location.
  • Mixed-use buildings with flats above are where smoke, odour and fan noise complaints usually start. Discharge as high and as far from windows as you can, and consider odour control from day one rather than after a complaint.
  • Shared cloud kitchen facilities may provide a common exhaust. Confirm the airflow allotted to your station and who pays for cleaning.

Record what was agreed in the lease or a letter. It protects you if the building management changes later.

Fire risk and suppression

Kitchen fires usually start at the cooking line and travel through grease in the hood and duct. Layers of protection:

  1. Baffle filters cleaned on schedule
  2. Hood fire suppression system (wet-chemical type, with nozzles over each appliance and in the plenum and duct, and an automatic gas shut-off). Indian listings mostly range from ₹50,000 to ₹1.6 lakh depending on size and nozzle count.
  3. Portable extinguishers suitable for cooking oil fires (commonly called Class K or wet-chemical types)
  4. Gas leak detection with an automatic shut-off valve
  5. Fire-rated duct routing where the duct passes through other areas

Your fire NOC requirements depend on your building and seating. See our fire NOC for restaurants in Delhi guide, and find vendors on our fire safety and CCTV page. Licences beyond fire are covered in our restaurant licences list for Delhi.

Cleaning frequency

NFPA 96 sets inspection intervals for grease build-up in the hood, duct and fan, with cleaning done whenever build-up is found:

Type of cooking Inspection interval (NFPA 96)
Solid fuel (wood, charcoal) Monthly
High volume: 24-hour, charbroiling, wok cooking Quarterly
Moderate volume Semi-annually
Low volume (seasonal, occasional) Annually

In practice for Indian restaurants:

  • Daily: wipe hood surfaces and empty grease cups
  • Weekly or more often: soak and degrease baffle filters (daily for heavy wok, tandoor or fry menus)
  • Every 3–6 months: professional hood, duct and fan cleaning, depending on menu and volume
  • Keep records: date, areas cleaned, before and after photos. Insurers, fire auditors and mall operators may ask.

Indian listings for kitchen exhaust duct cleaning are commonly priced around ₹3–₹6 per sq ft of duct surface, with hood-only deep cleaning priced higher. Rates vary a lot by access and grease level. Find providers on our deep cleaning page, or look at deep cleaning services in Noida and Gurgaon.

Cleaning log template

A simple log kept near the hood makes inspections easier and shows patterns, such as filters clogging faster after a menu change.

Date Area Task Done by Grease level (low/medium/high) Photo taken? Remarks
Hood surface Wipe and degrease
Baffle filters Soak and scrub
Grease cups Empty and clean
Duct sections Professional cleaning
Fan and housing Clean, check belt
ESP plates (if fitted) Wash and dry

Keep the professional cleaner's report with photos and a list of areas they could not reach. Unreachable sections are a sign you need more access doors. Hygiene logs also support your FSSAI inspections; our pest control guide explains why grease build-up attracts pests.

Maintenance schedule

Frequency Task
Daily Wipe hood, empty grease cups, check fan is running smoothly
Weekly Degrease filters; inspect for grease dripping at joints
Monthly Check fan belt tension and bearings; clean fresh-air filters; test gas leak detector
Quarterly Professional cleaning for high-volume and wok kitchens; ESP plate cleaning; check suppression system pressure gauges
Half-yearly Professional cleaning for moderate-volume kitchens; motor and electrical check
Yearly Suppression system service by the installer; full system review after any menu change

Many restaurants bundle exhaust cleaning with equipment servicing. You can find technicians on our kitchen repair and AMC page.

Cost summary (approximate, Delhi NCR, as of 2026)

Component Approx. range Notes
SS exhaust hood ₹2,300–₹5,500 per running foot Hood only; some high-capacity units listed higher
Ducting Per running foot or per sq ft quote Depends on material, thickness, length and bends
Exhaust fan Get quotes Size by airflow and static pressure
Fresh-air unit Get quotes Size against exhaust volume
Wet-chemical hood fire suppression ₹50,000–₹1.6 lakh Varies with hood length and nozzles
Kitchen ESP From about ₹1.2 lakh (one listing) Plus installation and plate cleaning
Duct cleaning Around ₹3–₹6 per sq ft Hood-only cleaning priced higher

These are seller listing prices, not installed project costs. Ask for one turnkey quote covering hood, filters, duct, fan, fresh air, electricals, suppression and installation, with drawings.

You can post one requirement and get quotes from up to 3 rated exhaust and ducting vendors, or browse kitchen exhaust and ducting vendors in Delhi NCR. City pages are also available for exhaust and ducting vendors in Delhi and Ghaziabad.

How to compare exhaust quotes

Ask each vendor to quote the same scope. Put them side by side:

Compare Vendor A Vendor B Vendor C
Hood length, overhang and material grade
Filter type and count
Design airflow (CFM or CMH) and duty level used
Duct material, thickness and joint type
Duct length, bends and access doors
Fan type, airflow and static pressure
Fresh-air unit included?
ESP, scrubber or odour filter included?
Fire suppression included?
Electrical work and controls included?
Installation, terrace work and civil openings included?
GST shown separately?
Warranty and first cleaning visit
AMC price

A quote that gives only a hood price per foot is not comparable with a full-system quote. Ask for the airflow calculation behind each proposal.

Warranty and AMC terms

Get these in writing:

  • Warranty on the fan motor and blower, and whether it covers labour
  • Warranty on fabrication workmanship, such as weld leaks
  • Whether the first professional cleaning visit is included
  • AMC scope: number of cleaning visits, fan servicing, ESP plate cleaning, report with photos
  • Response time for breakdowns, especially fan failure during service hours
  • Suppression system service frequency and who certifies it

Installation checklist

Before installation:

  • Cooking line finalised and appliance sizes confirmed
  • Hood drawing approved with length, overhang and height
  • Duct route agreed with interior contractor and landlord
  • Discharge point approved; away from windows and neighbours
  • Openings in walls, slabs or windows marked and permitted
  • Electrical supply for fans ready, with correct rating

During and after installation:

  • Duct joints welded or sealed as quoted
  • Access doors fitted at bends and long runs
  • Fan mounted on anti-vibration mounts, with safe access for servicing
  • Fresh-air unit installed and balanced against exhaust
  • Airflow checked at the hood with all appliances running
  • Suppression nozzles positioned over each appliance and the duct
  • Gas shut-off interlock tested
  • Drawings, warranty cards and cleaning instructions handed over

Coordinate with restaurant interior contractors in Delhi NCR so the false ceiling leaves access to the duct.

Common mistakes to avoid

  • Sizing the hood shorter than the cooking line to save money
  • Buying a fan by HP instead of airflow and static pressure
  • No fresh-air supply, so the kitchen runs hot and smoke spills out
  • Ducts with no access doors, so they can never be properly cleaned
  • Discharging exhaust near neighbours' windows or your own AC fresh-air intake
  • Treating the ESP as fit-and-forget
  • Finalising interiors before the duct route is fixed
  • Adding wok burners or a fryer later without rechecking airflow
  • Using a light-duty system sized for a café under an Indo-Chinese menu
  • Keeping no cleaning records

Quick checklist

  • Cooking line finalised before the hood is designed (see our kitchen equipment checklist)
  • Hood covers the full cooking line with overhang on open sides
  • Removable baffle filters specified
  • Airflow calculated by duty level and hood length
  • Duct material, thickness and welded or sealed joints written into the quote
  • Cleaning access doors at bends and long runs
  • Fan quoted by airflow (CMH) and static pressure
  • Fresh-air supply sized by an engineer
  • Discharge point approved by landlord or mall; away from neighbours
  • Pollution control (ESP, scrubber or odour filter) checked with DPCC or your state board and landlord
  • Wet-chemical hood suppression and suitable extinguishers installed
  • Gas leak detector with auto shut-off
  • Cleaning schedule, log and AMC in place

When you are ready, post your exhaust and ducting requirement and compare up to 3 quotes.

Sources

FAQs (22)

How much does a commercial kitchen exhaust hood cost in Delhi NCR?

Public seller listings for stainless steel hoods mostly fall between about ₹2,300 and ₹5,500 per running foot for the hood alone, as of 2026. Ducting, exhaust fan, fresh-air unit, fire suppression, electrical work and installation are usually extra, so compare full-system quotes rather than per-foot hood prices.

Which is better for kitchen ducting: GI, MS or stainless steel?

Many Indian kitchens use GI or MS ducting to save cost, while stainless steel resists corrosion better. The US fire code NFPA 96, widely used as a reference, specifies welded, liquid-tight grease ducts of at least 1.37 mm carbon steel or 1.09 mm stainless steel. Ask your vendor which standard they build to and check your mall, landlord or fire consultant's requirements.

How often should a restaurant kitchen exhaust be cleaned?

NFPA 96 sets inspection intervals of monthly for solid-fuel cooking, quarterly for high-volume cooking such as 24-hour, charbroil or wok cooking, semi-annually for moderate volume and annually for low volume, with cleaning done when grease build-up is found. Hood filters themselves usually need degreasing weekly or more often.

Do I need fresh air (make-up air) in my kitchen?

Yes. A strong exhaust pulls out large volumes of air, and without fresh air supply the kitchen becomes hot, doors slam or whistle, burners may burn poorly and smoke can spill into the dining area. A mechanical engineer or experienced vendor should size the fresh-air supply against your exhaust volume.

What is an ESP in a kitchen exhaust system?

An electrostatic precipitator (ESP) uses charged plates to trap fine smoke and grease particles before the air leaves the duct. It is used where visible smoke, odour or neighbour complaints are a concern, and plates need regular cleaning to keep working.

Is an ESP or scrubber mandatory for restaurants in Delhi?

We could not verify a single citywide rule that makes ESPs or scrubbers mandatory for every restaurant. Requirements can come from Delhi Pollution Control Committee directions, consent conditions, mall or landlord rules, or complaint-driven notices. Check with DPCC and your landlord before you finalise the design.

Can I use a coal tandoor in a Delhi restaurant?

In December 2025, the Delhi Pollution Control Committee ordered a ban on coal and firewood tandoors at hotels, restaurants and eateries, asking them to switch to electric, gas or other clean-fuel options. Check the current status of the order with DPCC before planning any solid-fuel cooking.

Why is a dirty exhaust duct a fire risk?

Grease vapour condenses inside hoods and ducts. If a flare-up reaches that layer, fire can travel through the duct and spread beyond the kitchen. Regular cleaning, baffle filters, a hood fire suppression system and fire-rated duct routing reduce the risk.

How much does a kitchen hood fire suppression system cost?

Indian seller listings for wet-chemical kitchen hood suppression systems mostly range from about ₹50,000 to ₹1.6 lakh as of 2026, depending on hood length, nozzle count and brand. Installation and GST may be extra.

What is the difference between a kitchen chimney and a commercial exhaust hood?

A home chimney is a self-contained unit with a small motor and filters, designed for a few burners and light cooking. A commercial exhaust system is a hood, duct, separate fan and fresh-air supply sized for continuous high-heat cooking. Indian sellers sometimes list commercial hoods as chimneys, so check what the quote actually includes.

How do I convert CFM to CMH for an exhaust fan?

One cubic foot per minute (CFM) is about 1.7 cubic metres per hour (CMH). So a 3,000 CFM requirement is roughly 5,100 CMH. Indian fan quotes are often in CMH, while many hood guides use CFM, so convert before you compare.

Why does my kitchen exhaust make so much noise?

Noise usually comes from an undersized duct with high air velocity, a fan without anti-vibration mounts, loose duct supports or a fan running at full speed when it does not need to. A speed controller, proper mounting and correctly sized ducts reduce it. Terrace fans near homes need extra attention to avoid complaints.

Why is smoke coming into my dining area?

Common reasons are a hood that is shorter than the cooking line, too little exhaust airflow, clogged filters, or no fresh-air supply so the kitchen pulls air from the dining room unevenly. Cross-drafts from fans or AC vents near the hood can also push smoke out. A vendor can measure airflow and check the balance.

Can kitchen exhaust ducting go through a false ceiling?

It often does, but grease ducts need clearance from combustible materials, access doors for cleaning, and fire-rated protection where they pass through other areas. Plan the route with your interior contractor and fire consultant before the ceiling is closed, so cleaners can reach every section later.

How long does a kitchen exhaust installation take?

Timelines depend on duct length, building access, terrace work and whether the hood is fabricated or ready-made. Ask each vendor for a written schedule covering fabrication, installation and commissioning. Coordinate it with interiors, since false ceiling and tiling work affect the duct route.

Do cloud kitchens need a full exhaust system?

Yes, if they cook with gas, tandoor, fryers or woks. Cloud kitchens often run long hours with high volume, which makes grease build-up and heat worse. Shared cloud kitchen facilities may provide a common exhaust, so check what is included before you install your own.

What is a grease trap and is it part of the exhaust system?

A grease trap sits in the drain line and catches fats and oils from sinks before they block sewers. It is not part of the air exhaust, but both handle grease and need regular cleaning. Many kitchens schedule grease trap cleaning alongside filter and hood cleaning.

Should I buy a water-wash hood?

Water-wash hoods automate part of the grease cleaning inside the hood and suit very high-grease, high-volume kitchens. They cost more and need water, drainage and controls. Most small and mid-size Indian restaurants manage with removable baffle filters and a strict cleaning schedule.

What AMC should I take for kitchen exhaust?

A useful exhaust AMC covers scheduled hood and duct cleaning, fan belt and bearing checks, motor inspection and a cleaning report with photos. If you have an ESP, include plate cleaning and electrical checks. Agree the visit frequency based on your menu and volume.

Does the exhaust fan need a separate electrical connection?

Larger centrifugal exhaust and fresh-air fans often need a dedicated circuit and sometimes three-phase supply. Check the motor rating with your electrician and include it in your total sanctioned load. Interlocking the fan with the gas supply or suppression system should be discussed with your fire consultant.

How far should the hood extend beyond the cooking equipment?

The US International Mechanical Code requires Type I canopy hoods to extend at least 6 inches beyond the cooking surface on all open sides. Many vendors use this as a reference in India. Longer overhangs improve capture for high-heat appliances.

Can I install the exhaust fan on the terrace of a residential building?

It depends on your lease, the building's rules and local permissions, and it is a common source of RWA complaints. Discharge should be away from windows, fresh-air intakes and neighbours. Get the landlord's written consent and check with your fire consultant before work starts.